BACKFLOW PREVENTION ASSEMBLY BPAT

TESTER FINAL EXAM LATEST ACTUAL

EXAM QUESTIONS AND CORRECT

DETAILED ANSWERS (VERIFIED ANSWERS)

Pressure vacuum breaker shut-off valves must be _____ valves.

  • Angle
  • Gate
  • Globe
  • Regulating
  • Tightly closed Correct Answer E. Tightly closed

An indication that a pressure vacuum breaker is undersized for its application is _____?

  • Air-inlet valve leakage
  • Bonnet distortion
  • Chatter or noise during flow
  • Disc pitting
  • Spring elongation Correct Answer C. Chatter or noise during
  • flow

Continuous flow from a pressure vacuum breaker's test cock 2 with shut-off valve 2 open and shut-off valve 1 closed is an indication of _____?

  • Backpressure backflow
  • Backsiphonage backflow
  • A failed air-inlet valve
  • A leaking check valve
  • A leaking or damaged shut-off valve 1 Correct Answer A.
  • Backpressure backflow

  • / 3

Pressure vacuum breakers may be used on the following applications except ____?

  • High hazard/backsiphonage
  • High hazard/continuous pressure
  • Low hazard/backpressure
  • Low hazard/backsiphonage
  • Low hazard/intermittent pressure Correct Answer C. Low
  • hazard/backpressure

A double check valve assembly is installed 12 in. (30.5 cm) above the floor for _____?

  • Electrical code compliance
  • Floor draining
  • Maintenance
  • Mechanical code compliance
  • Rodent control Correct Answer C. Maintenance

Double check valve assembly product performance standards require venting for _____?

  • Chemicals
  • Test cock corrosion
  • Trapped air
  • Vertical installations
  • Winterization Correct Answer C. Trapped air

A low-hazard use only backflow preventer is a(n) _____?

  • Air-gap separation
  • Atmospheric vacuum breaker
  • Double check valve assembly
  • Pressure vacuum breaker assembly
  • Reduced pressure principle assembly Correct Answer C.
  • Double check valve assembly

Double check detector assembly flow indicators must register flow up to _____? 2 / 3

  • 1 gpm (3.8 l/min)
  • 2 gpm (7.6 l/min)
  • 3 gpm (11.4 l/min)
  • 4 gpm (15.1 l/min)
  • 5 gpm (18.9 l/min) Correct Answer B. 2 gpm (7.6 l/min)

A field test report for a double check valve assembly will include the manufacturer's name, model, size, and _____?

  • Body material
  • Date of manufacture
  • Serial number
  • Working pressure (maximum)
  • Working temperature (maximum) Correct Answer C. Serial
  • number

Double check valve assembly components must be _____?

  • Bronze
  • Independently acting
  • Plastic
  • Rubber
  • Spring activated Correct Answer B. Independently acting

After the repair of a double check valve assembly, a field test is required for the _____?

  • Check valve number 1
  • Component repaired
  • Entire assembly
  • Tester's personal records only
  • Shut-off valve tightness Correct Answer C. Entire assembly

Prior to testing the check valves in the direction of flow on a double check valve assembly using a high and low side on the gauge, a tester must first ____?

  • Determine the tightness of shut-off valve number 2
  • Notify the owner of the water shut-off
  • / 3

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: EXAM ELABORATIONS
Added: Sep 7, 2025
Description:

BACKFLOW PREVENTION ASSEMBLY BPAT TESTER FINAL EXAM LATEST ACTUAL EXAM QUESTIONS AND CORRECT DETAILED ANSWERS (VERIFIED ANSWERS) Pressure vacuum breaker shut-off valves must be _____ valves. A. Ang...

Get this document $30.00