DC Boiler Exam Prep 2024 Update 215+ Questions and Verified Correct Answers Already Graded A+ _____ keeps the hardness in boiler water in solution so that it cannot settle out on the

heating surfaces. - CORRECT ANSWER: Chelants

______ cause hardness particles in boiler water to precipitate as heavy sludge that is

removed through the bottom blow. - CORRECT ANSWER: Phosphates

_______ in boiler water contributes to the formation of CO2. - CORRECT

ANSWER:High Alkalinity

#2 fuel oil contains approximately ______ Btu/gal - CORRECT ANSWER: 141,000

#6 fuel oil contains approximately _____ Btu/gal - CORRECT ANSWER: 155,000

% of oxygen in air - CORRECT ANSWER: 21%

  • BHP = x ft² of heating surface (general) - CORRECT ANSWER: 10 ft² heating surface

1 Boiler Horsepower = x Btu/hr - CORRECT ANSWER: 33,475 Btu/hr

1 Boiler Horsepower = x lbs of steam generator per hour - CORRECT ANSWER: 34.5

lbs/hr

1 lb of chemical to 1000 gallons of water = x ppm - CORRECT ANSWER: 120 ppm

A ____ amine is injected into a boiler during operation to raise the pH of the

condensate. - CORRECT ANSWER: Neutralizing

A _____ test is a test that determines the concentration of a specific dissolved

substance. - CORRECT ANSWER: Titration

A 10°F rise in feed water temperature results in a ____ increase in efficiency -

CORRECT ANSWER: 1%

A dearator stores how much feedwater? - CORRECT ANSWER: 20-30 minutes supply

A demineralizer is usually used with ____ pressure boilers - CORRECT ANSWER: High

A flash tank____ - CORRECT ANSWER: Recovers low pressure steam

A reciprocating pump is a ___ type pump. - CORRECT ANSWER: positive

displacement 1 / 2

A saybolt viscometer is used for _____. - CORRECT ANSWER: testing and grading of oils

A single element feedwater heater responds to ____ - CORRECT ANSWER: water

level

A steam pressure gauge can be calibrated with a _____. - CORRECT

ANSWER:deadweight tester

A steam pressure gauge should have a range at least _____. - CORRECT

ANSWER:1-1/2 times the safety valve setting

A sudden increase in stack temperature without a corresponding increase n steam

demand indicates what? - CORRECT ANSWER: a broken baffle

A three element feedwater heater responds to ____ - CORRECT ANSWER: water level, steam flow, & feedwater flow

A two element feedwater heater responds to ____ - CORRECT ANSWER: water level & steam flow

A(n) _____ analysis is used to determine the percentage of various elements contained in coal, including carbon, oxygen, nitrogen, hydrogen, sulphur, and ash. - CORRECT

ANSWER:ultimate

A(n) _____ test is performed on a boiler to check the operation of the low water fuel cutoff by allowing the water level in the boiler to drop slowly. - CORRECT

ANSWER:Evaporation

Above ____°F & ______ psi a hot water boiler is considered "high pressure" -

CORRECT ANSWER: 250°F & 160 psi

According to ASME Code how often should a boiler be blown down when no boiler

water analysis is done? - CORRECT ANSWER: every 24 hours

According to ASME Code, a boiler pressure gauge should have a range of - CORRECT

ANSWER:1-1/2 - 2 times the safety valve setting

According to ASME code, the maximum size of the boiler bottom blowdown line is

_____. - CORRECT ANSWER: 2-1/2"

According to ASME Code, what must a boiler with more than 500 ft² of heating surface

have? - CORRECT ANSWER: two or more safety valves

  • / 2

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 15, 2025
Description:

DC Boiler Exam Prep 2024 Update 215+ Questions and Verified Correct Answers Already Graded A+ _____ keeps the hardness in boiler water in solution so that it cannot settle out on the heating surfac...

Get this document $30.00