California UST service technician part 2 Exam Questions and Answers when an automatic tank gauge is utilized for singlewall Tank leak detection it shall generate A post test hard copy data
report of the following information EXCEPT: - Correct
Answers ✅Outside air temperature.Approved cathodic protection methods include? - Correct Answers ✅Sacrificial anodes Impressed current systems Cathodic protection systems must be inspected by a certified cathodic protection tester within ___ months of installation - Correct Answers ✅6 UST include the following? - Correct Answers ✅500 gallon waste oil
Motor vehicle fuel tanks include the following EXCEPT: -
Correct Answers ✅Waste oil tanks Enhanced line leak detection test methods must be capable of detecting a leak rate of at least? - Correct Answers ✅.005 gph The following are approved method of release detection for
singlewall tanks EXCEPT: - Correct Answers ✅Interstitial
monitoring