Fdny p-99 c of f Latest Update 2025-2026 Actual Exam 90 Questions with 100% Verified Correct Answers Guaranteed A+ Verified by Professor

At what pressure is the oil and air mixture delivered to the nozzle? - CORRECT

ANSWER: 1-15 psi

At what pressure should oil storage tanks be tested? - CORRECT ANSWER: At 1 1/2x max working pressure but never < 25 psi

At what pressure should piping be tested? - CORRECT ANSWER: 1/2 max working

pressure but less than pressure required for storage tank

At what temperature is oil stored at? - CORRECT ANSWER: Just above 100 degrees

Can oil burn? Why or why not? - CORRECT ANSWER: No it is a liquid fuel and must be changed into a gas or vapor to burn

How are flue dampers designed? - CORRECT ANSWER: So that they cannot

completely cut off passage of flue gasses at any time

How is oil heated in storage tanks? - CORRECT ANSWER: Coils using low pressure hot water/steam or approved electric heaters.

How long should hydrostatic pressure be maintained? - CORRECT ANSWER: Until all

joints and connections are inspected for leaks and at 30 minutes have passed

How much air do burners require per gallon of oil burner? - CORRECT ANSWER: 2000 cubic feet 1 / 2

How much cfm of air be capable of per gallon of oil per hour? - CORRECT ANSWER:

36 cfm

How often should a boiler be inspected? - CORRECT ANSWER: Once a year

How often should nozzles and rotary cups be cleaned on a no. 6 oil burner? -

CORRECT ANSWER: Daily

If ventilation is supplied mechanically, what is required of the pressure? - CORRECT

ANSWER: It must be greater than the atmospheric pressure outdoors

Is a chimney required to install a burner? - CORRECT ANSWER: Yes

What are the 4 safety controls implemented? - CORRECT ANSWER: Oil temperature

control, ignition, stack/combustion control, and high pressure and temperature control.

What can be a result of insufficient air supply? - CORRECT ANSWER: Dense, black

smoke and soot

What can happen if a combustion chamber is not preheated? - CORRECT ANSWER:

Oil burner system gets filled with vaporized oil fumes. Indicated by strong odor

What can happen to the flame of there is an excess air supply? - CORRECT ANSWER: The flame can go out

What can lead to after drip? - CORRECT ANSWER: A defective oil cut off valve, allows oil to drip into combustion chamber while burner is off. Carbon build up.

  • / 2

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 27, 2025
Description:

Fdny p-99 c of f Latest Update 2025-2026 Actual Exam 90 Questions with 100% Verified Correct Answers Guaranteed A+ Verified by Professor At what pressure is the oil and air mixture delivered to the...

Get this document $30.00