Residential Electrical Scope E3401.2 - Answer-Limited to 120/240 volt, 0-400 ampere, single phase systems in one and two family dwellings and accessory structures.
Residential Electrical Limitations E3401.3 - Answer-Does not cover Installations, including associated lighting, under the exclusive control of communications utilities and electric utilities, or services over 400 amperes.
Integrity of electrical equipment E3404.7 - Answer-Internal parts of electrical equipment, including busbars, wiring terminals, insulators, and other surfaces shall not be damaged or contaminated by foreign materials such as PAINT, plaster, cleaners, abrasives, and corrosive residues.
- / 3
- | P a g e
Working clearances E3405 - Answer-36 inches deep, 30 inches wide, and floor to 6.5 feet with minimum 90 degree opening doors
Panelboards and Service Equipment Locations 3405.5 - Answer-Shall not be located in bathrooms, toilet rooms, clothes closets, or over the steps of a stairway.
Minimum size of conductors E3406 - Answer-14 AWG copper and 12 AWG aluminum or copper clad aluminum.
Length of conductor for splice or termination 3406.11.3 - Answer-minimum 6 inches of free conductor or 3 inches outside of each opening.
Tightening torque values E3406.12 - Answer-are provided by the manufacturer to be achieved by approved means (torque wrench, torque screwdriver) indicated in inch pounds.
Methods not permitted for connections E3406.14.2 - Answer-connection devices or fittings that depend soley on solder shall not be used. 2 / 3
- | P a g e
Grounded Conductor Identification E3407 - Answer-
Neutrals: continuous white or gray outer finish or three
continuous white or gray stripes along it or at terminations, on any other sheathing color except green insulation.
Festoon Lighting NEC 225.6 - Answer-A sting of outdoor lights that are suspended between 2 points. Shall not be smaller than 12 AWG unless the conductors are supported by messenger wires and across spans not more than 40 feet without messenger wires.
Ceiling-supported paddle fans shall be supported _____ of the outlet box - Answer-independently
E4101.6
Above-ground service-entrance cables subject to physical damage shall be protected by Schedule ___ PVC conduit - Answer-Schedule 80 or rigid metal conduit, intermediate conduit, electrical metallic tubing, or other approved means.
E3605.5