Journeyman electrician exam prep Latest Update 2024-2025 Actual Exam Questions and 100% Verified Correct Answers Guaranteed A+

110.26 (E) discusses the space equal to the width and depth of the equipment and extending from the floor to a height of six feet above the equipment or to the structural

ceiling. What is this called? - CORRECT ANSWER: Dedicated electrical space

240.22 states no over current device shall be connected in series with any conductors -

CORRECT ANSWER: The overcurrent device opens all conductors of the circuit,

including the grounded and is designed so no pole can operate independently.

250.54(G) states when driving a ground rod and solid rock is encountered, the ground rod is permitted to be buried in a trench at least how deep? - CORRECT ANSWER: 30 inches

250.97 Exception 2 in the NEC says for circuits over _____ to ground, the electrical continuity of RMC that contain any conductor, other than service conductors, shall be isured with 2 locknuts, one inside and one outside of boxes and cabinets - CORRECT

ANSWER: 250 volts

300.6 says that where corrosion protection is necessary and the conduit is threaded in the field, the threads shall be coated with what? - CORRECT ANSWER: An electrically conductive, corrosion resistant compound

314.28(A)(1) states that straight pulls in pull boxes with conductors size 4 AWG or larger, box length should be greater than or equal to times the trade diameter of the

largest conduit entering box. - CORRECT ANSWER: Eight

314.72(E) states that a suitable cover to cover an underground box is considered to

weigh what and shall have what written on it? - CORRECT ANSWER: 100 pounds

"Danger - High Voltage - Keep out"

  • / 2

332.30 states that type MI cable shall be supported at intervals of at least how many

feet? - CORRECT ANSWER: Six feet

422.13 states fixed storage water heaters with a capacity of ____ gallons should be

considered a continuous load for sizing branch circuits - CORRECT ANSWER: 120

gallons

430.32 gives percentages for marked service factors on motors. For 40 degrees C or

less and 1.15, what is the percentage you multiply by? - CORRECT ANSWER: 125%

An enclosure that contains a device (s) shall have a weight supported by a single conduit that does not exceed ________ lbs.

314.23(f)(e) - CORRECT ANSWER: 20 lbs

Any motors that supply a motor used in a short time, intermittent, or varying duty application are permitted to have an ampacity of not less than the percentage values on

table _______ and called what? - CORRECT ANSWER: 430.22(E) Duty Cycle Service

Ceiling suspended (paddle) fans weighing MORE than ____ pounds shall be supported

independently of the outlet box - CORRECT ANSWER: 70 pounds

Chapter 9 note 4 states conduit nipples less than 24 inches can fill to a max of their

cross sectional area - CORRECT ANSWER: 60 percent

Class ____ locations are those that are hazardous because of combustible dust -

CORRECT ANSWER: Class II

Class _____ locations are those in which flammable gases, flammable liquid produced vapors, or combustible liquid produced vapors are present that are explodable. -

CORRECT ANSWER: Class 1

Class _____ locations are those that are hazardous because of the presence of easily ignitible fibers or materials producing combustible flyings.

  • / 2

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: EXAM ELABORATIONS
Added: Aug 30, 2025
Description:

Journeyman electrician exam prep Latest Update 2024-2025 Actual Exam Questions and 100% Verified Correct Answers Guaranteed A+ 110.26 (E) discusses the space equal to the width and depth of the equ...

Get this document $30.00