What is the primary function of a refrigerant distributor at the outlet of a thermostatic expansion valve?
- Allow the evaporator to operate with proper superheat.
- Feed the evaporator sufficient liquid to control the leaving air
- Decrease the pressure drop across the evaporator coil.
- Evenly feed each evaporator circuit. - ANSWER- D
temperature.
The voltage that controls the operation of the contact points in a
potential relay is:
- Line voltage.
- Run-winding voltage.
- Back EMF.
- Control voltage. - ANSWER- C
Refrigerant migration can be minimized by the use of a(n)
- / 4
- Oil separator.
- Receiver tank.
- Liquid line solenoid valve.
- Crankcase pressure regulating valve. - ANSWER- C
A transformer rated at 40 VA at 24 volts output has a maximum capacity
of:
- 0.625 A.
- 0.960 A.
- 1.240 A.
- 1.667 A. - ANSWER- D
Using the illustration below, what is the pressure drop across the refrigerant distributor and distributor tubes?
- 2.5 psi.
- 35 psi.
- 71 psi.
- 120 psi. - ANSWER- B
The current that opens the contacts in the current relay is the:
- Start-winding current. 2 / 4
- Run-winding current.
- 24-volt applied voltage.
- Back EMF. - ANSWER- D
The holding coil of the potential start relay is connected across:
- The run-winding and common.
- The start-winding and common.
- Both run and start windings.
- The line voltage. - ANSWER- B
In a pump-down refrigeration system, the compressor is cycled on and
off by the:
- Temperature control.
- Low pressure control.
- Head pressure control.
- Liquid solenoid valve. - ANSWER- B
Low ambient head pressure controls in a condensing unit function by
controlling flooding of liquid refrigerant in the:
- Receiver.
- Accumulator. 3 / 4
- Evaporator.
- Condenser. - ANSWER- D
As head pressure increases while suction pressure remains constant, the
compressor current:
- Increases and capacity increases.
- Decreases and capacity increases.
- Increases and capacity decreases.
- Increases and capacity remains constant. - ANSWER- B
On an inside 30 lb. receiver with a safety-pressure relief device, the
discharge of the safety device should be piped to the:
- Inside compressor.
- Outside condenser.
- Outside atmosphere.
- Inside evaporator. - ANSWER- C
On a new installation, the purpose of adjusting a thermostatic expansion
valve to maintain a low superheat is to ensure that:
- The liquid refrigerant will boil off as quickly as possible in the
- / 4
evaporator.