- | P a g e
NICET LEVEL 2 NEWEST 2025 ACTUAL EXAM
COMPLETE 100 QUESTIONS AND CORRECT
DETAILED ANSWER S (VERIFIED ANSWER S)
|ALREADY GRADED A+ (BRAND NEW
VERSION!)
Question: Where replacing residential sprinklers manufactured
prior to 2003 that are no longer available from the manufacturer and are installed using a design density less than 0.05 gpm/ft2, a residential sprinkler with an equivalent K-factor (+/- ______ percent) shall be permitted to be used provided the currently listed coverage area for the replacement sprinkler is not exceeded.
Answer : 5
Question: Consider a standpipe and hose system with a
hydraulic design information sign. When inspecting the information sign, where should it be located for automatic and semi-automatic systems?
Answer : Secured to the water supply control valves
Question: Dry barrel and wall hydrants shall be inspected
______ and after each operation?
Answer : Annually
- | P a g e
Question: Which of the following would be considered
noncritical deficiency? (Select 3)
- A hose rack that only swings out of the cabinet 120 degrees
- A hose/hydrant house not fully equipped
- A hose on standpipe that is not connected
- A hose connection on a pressure reducing valve with a
missing cap
Answer : B. A hose/hydrant house not fully equipped
- A hose on standpipe that is not connected
- A hose connection on a pressure reducing valve with a
missing cap
Question: When inspecting a diesel fire pump, the fuel tank
shall be at least ______ full?
Answer : Two thirds
Question: Consider a water storage tank with a low temperature
alarm connected to a constantly attended location. What is the inspection frequency for the water temperature?
Answer : Quarterly
Question: What is the visual inspection frequency of a room
temperature supervisory signaling switch?
- | P a g e
Answer : Quarterly
Question: All pressure gauges used for hydrant testing should be
calibrated at least every _______ or more frequently depending on use?
Answer : Year
Question: While conducting a full flow trip test of a dry pipe
system, the tester at the inspector's test valve notes the time when water flows steadily from the test connection. This time is noted for comparison purposes for previous tests. Which of the following is true regarding water delivery?
Answer : NFPA 13 does not require water delivery in 60
seconds for all systems
Question: Each portable wooden ladder shall support at least
_____ times the maximum intended load?
Answer : 4
Question: A section of piping on a standpipe system has been
replaced. As a result, the system shall be hydrostatically tested in conformance with NFPA ____?
Answer : 14
- | P a g e
Question: When measuring the pitot pressure of a stream of
practically uniform velocity, the orifice in the pitot tube is held down stream approximately _____ the diameter of the hydrant outlet or nozzle opening and in the center of the stream?
Answer : one-half
Question: Which of the following conditions does not require
sprinkler replacement?
- loading
- loss of fluid in the glass bulb
- Matriculation
- All of these conditions require replacement
Answer : C. Matriculation
Question: Consider testing a low air pressure switch on a dry
pipe system. The procedure is to operate the switch and verify receipt of the signal is obtained where the required pressure is increased or decreased a maximum _____ PSI from the required pressure level?
Answer : 10
Question: The reading of a pressure gauge at the discharge of
the pump converted to feet of liquid, and referred to datum, plus