S12 Sprinkler Chart Exam (Latest 2024 / 2025 Update) Questions and Verified Answers | 100% Correct | Grade A
Question:
During an operational test of a foam water sprinkler system, if the nozzles are plugged what color tag is used?
Answer:
Red
Question:
Steel water storage tanks without corrosive protection are to be inspected how often?
Answer:
- years
- / 4
Question:
A sprinkler head with a white frame has a temperature rating of?
Answer:
175 - 225°F
Question:
The weekly test of an electric fire pump is how long?
Answer:
10 minutes
Question:
The weekly test of a Diesel fire pump is how long?
Answer:
30 minutes
Question:
Upon inspection of a sprinkler system, if the hydraulic nameplate is missing what color tag is used?
Answer:
Yellow
- / 4
Question:
When inspecting a preaction system, if the electrical components are not in service what color tag is used?
Answer:
Red
Question:
Vane type water flow devices shall be tested how often?
Answer:
Semi-annually
Question:
Proper number of spare heads and wrenches shall be inspected how often?
Answer:
Annually
Question:
The temperature rating of a sprinkler head with a green glass bulb is?
Answer:
175 - 225°F
- / 4
Question:
When inspecting a sprinkler system if the spare sprinkler cabinet is missing what color tag should be used?
Answer:
Yellow
Question:
On a dry pipe sprinkler head if no tests were conducted in 12 years what color tag should be used?
Answer:
Orange
Question:
Red Tag
Answer:
Impairment (Notify FDNY, shall be fixed immediately)
Question:
Orange Tag
Answer:
Critical Deficiency (Notify FDNY if not fixed after 30 days)
- / 4