STATE OF OHIO FIRE
ALARM TEST - STUDY
GUIDE QUESTIONS
WITH PASSED
ANSWERS!!
OHIO FIRE ALARM
Evatee10/17/24OHIO FIRE ALARM 1 / 2
STATE OF OHIO FIRE ALARM TEST - STUDY
GUIDE QUESTIONS WITH PASSED ANSWERS!!
spacing for smoke detectors or manufactured specs Answer - rule of thumb - 30ft manual pull station height Answer - 3-1/2 to 4-1/2 ft secondary power must turn of within ? seconds on loss of primary supply Answer - 10 seconds manual pull stations must be mounted within ? feet of exits on each floor and spaced up to ? Answer - 5 ft, 200 ft residential, secondary power supply time Answer - 24 hours in normal, 4 minutes of full alarm commercial, secondary power supply time Answer - 24 hours in normal, 5 minutes of full alarm live voice, secondary power supply time Answer - 24 hours in normal, 15 minutes of full power audible device decibels, public Answer - 75 db minimum or 15 above ambient audible device decibels, private Answer - 45 db or 15 db above ambient