U3 ICC Tank Tightness Testing Exam

Study Guides Aug 18, 2025
Loading...

Loading document viewer...

Page 0 of 0

Document Text

U3 ICC Tank Tightness Testing Exam Questions and Answers (Latest Update) Verified Answers

Question 1: On a steel tank without cathodic protection, if a

coating is flawed, what happens at the flaw?

  • Cathodic surface is increased
  • Current flow is increased from this area
  • Current flow is increased to this area
  • Current flow is increased from this area

CORRECT ANSWER : b. Current flow is increased from

this area

Question 2: On an impressed current cathodic protection

system, the negative wire of the rectifier is connected to the:

  • Anode
  • Cathode
  • Drop tube
  • Dielectric union
  • Cathode

CORRECT ANSWER : b. Cathode

Question 3: All are examples of acceptable release detection

for tanks, except:

  • Impressed current cathodic protection
  • Automatic tank gauging
  • Statistical inventory reconciliation
  • Soil-vapor monitoring
  • Impressed current cathodic protection

CORRECT ANSWER : a. Impressed current cathodic

protection

Question 4: When a tank is temporarily closed, the cathodic

protection system:

  • Must be turned off
  • Must remain in operation
  • Should be removed
  • Operator can have it on or off.
  • Must remain in operation

CORRECT ANSWER : b. Must remain in operation

Question 5: When a steel tank is installed with a galvanic CP

system attached, the tank gauges are usually connected through a riser with a dielectric bushing. What is the purpose of that?

  • To prevent static discharge
  • To minimize effects of noise
  • To electrically isolate the tank from the tank gauge
  • To prevent water intrusion in the tank
  • To electrically isolate the tank from the tank gauge

CORRECT ANSWER : c. To electrically isolate the tank

from the tank gauge

Question 6: Factory-installed dielectric coatings may include

all of the following except:

  • Asphalt
  • Epoxies
  • Enamels
  • Fiberglass-reinforced plastic
  • Asphalt

CORRECT ANSWER : a. Asphalt

Question 7: According to the EPA, Tank tightness test data

must be maintained for:

  • 18 months
  • 3 years
  • 5 years
  • Until the next test is performed
  • Until the next test is performed

CORRECT ANSWER : d. Until the next test is performed

Question 8: How long must records of UST system repairs be

available on site?

  • 60 days
  • 1 year
  • 5 years
  • For the remaining lifetime of the UST system
  • For the remaining lifetime of the UST system

Download Document

Buy This Document

$30.00 One-time purchase
Buy Now
  • Full access to this document
  • Download anytime
  • No expiration

Document Information

Category: Study Guides
Added: Aug 18, 2025
Description:

U3 ICC Tank Tightness Testing Exam Questions and Answers (Latest Update) Verified Answers Question 1: On a steel tank without cathodic protection, if a coating is flawed, what happens at the flaw? ...

Get this document $30.00