NETA ETT Certified Level 3 Complete Test Questions

Question 1: A newly installed 4160V emergency generator has

an insulation resistance value of 150 Megohms after one minute with an equipment temperature of 32 degrees C. Is this value acceptable per NETA standards?

CORRECT ANSWER : No

Question 2: Which test method measures Hydrolyzable Flouride

content in SF6 gas?

CORRECT ANSWER : ASTM D2284 [Standard Test Method

for Acidity of Sulfur Hexafluoride]

Question 3: The operating speed of a protective relay is

dependent on:

  • Spring Tension
  • Armature core air gap
  • Rate of flux built up
  • | Page

CORRECT ANSWER : Spring Tension, Armature core air gap,

Rate of flux built up

Question 4: According to IEEE C57.106, which test is

recommended for routine acceptance of new, unprocessed oil from a supplier for use in circuit breakers?

CORRECT ANSWER : ASTM D877 [Standard Test Method for

Dielectric Breakdown Voltage of Insulating Liquids Using Disk Electrodes]

Question 5: Meter Sockets and meter disconnect switches

should generally be connected on what side of a service disconnecting means?

CORRECT ANSWER : The line side

Question 6: What size neutral resistor would be required to limit

the fault current of a 13,800-480Y/277V 1500kVA Transformer to 5A?

CORRECT ANSWER : 55.4

  • | Page

Question 7: Correcting the power factor of three-phase loads

normally involves adding (capacitance, inductance) in (series, parallel)

CORRECT ANSWER : capacitance in parallel

Question 8: The voltage induced into the armature of a DC

motor is known as the:

CORRECT ANSWER : CEMF [counter-electromotive force]

Question 9: As a battery cell starts discharging, internal

resistance of the cell will _____ .

CORRECT ANSWER: increase

Question 10: When conducting an ASTM D877 dielectric

breakdown test, the fluid is continuously stirred. True or False

CORRECT ANSWER : False

  • | Page

Question 11: What are the necessary requirements to operate

two transformers in parallel?

CORRECT ANSWER : * Same Phase Angle Shift

  • Same Polarity
  • Same Phase Sequence
  • Same Frequency

Question 12: What are the convenient (but not necessary)

requirements to operate two transformers in parallel?

CORRECT ANSWER : * Same voltage ratio and turns ratio

  • Same Percentage Impedance
  • Same KVA Rating
  • Same position of tap changer

Question 13: What is the maximum acceptable neutralization

number for a new 35kV power transformer filled with FR3 insulating liquid that was tested in accordance with ASTM D974?

Download Study Material

Buy This Study Material

$30.00
Buy Now
  • Immediate download after payment
  • Available in the pdf format
  • 100% satisfaction guarantee

Study Material Information

Category: CAREER EXAMS
Description:

NETA ETT Certified Level 3 Complete Test Questions Question 1: A newly installed 4160V emergency generator has an insulation resistance value of 150 Megohms after one minute with an equipment tempe...

Purchase PDF $30.00